| Plan Review Notes For Permit 22010362 |
| Permit Number |
22010362 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-31 17:14:06 | BUILDING PROVISO | | | | | | 1) IN ORDER TO DETERMINE IF THE ROOF STANDS ARE CAPABLE | | | OF WITHSTANDING THE REQUIRED WIND LOADS, THE SIZES OF | | | THE UNITS, THE CLEAR HEIGHT OF THE STANDS AND THE ROOF | | | ZONE IN WHICH THEY ARE LOCATED WILL HAVE TO BE | | | SPECIFIED. SUBMIT THIS INFORMATION ALONG WITH THE | | | APPROPRIATE ITEMS CIRCLED OR HI-LITED ON THE TABLES IN | | | THE PRODUCT APPROVALS AND THE GENERIC ENGINEERING. |
|