Plan Review Notes
Plan Review Notes For Permit 22010360
Permit Number 22010360
Review Stop E
Sequence Number 1
Notes
Date Text
2022-03-03 09:22:01ELECTRIC REVIEW FAILED
 1) PLAN DENOTES GENERATORS, THERE IS NO RECORD OF ANY
 GENERATORS PERMITTED ON THIS PROPERTY, PLEASE EXPLAIN
 OR REMOVE FROM DRAWING IF NONE EXISTS. FBC 107.2
 2) PLEASE DETAIL PANEL NC LOCATION ON SITE DRAWING.
 ENSURE CLEARANCES COMPLY WITH NEC REQUIREMENTS. FBC
 107.2
 3) PLEASE PROVIDE ELECTRICAL SPECIFICATIONS FOR NEW
 CHILLERS. FBC 107.2
 4) NO RECORD EXISTS OF MECHANICAL PERMIT TO INSTALL
 CHILLERS. PLEASE EXPLAIN. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  