| 2022-02-28 13:36:13 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL1654-R28 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO |
| | INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN |
| | BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE |
| | BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY. SELECT |
| | SYSTEM USED TO MEET MINIMUM DESIGN PRESSURE REQUIREMENT |
| | FOR EXPOSURE CATEGORY C AREA. (-108.17) |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL4595.19-R6 COVERS MULTIPLE FASTENER SPACING |
| | TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT |
| | FASTENER PATTERN & SPACING FROM TABLE ?A? PAGE #2 OF |
| | THE EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM |
| | DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE |
| | CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. SECOND REQUEST. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |