| 2022-11-16 18:03:29 | RESIDENTIAL (R3) GARAGE CONVERSION/ALTERATION THIRD |
| | BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22010353 |
| | 849 ARDMORE RD |
| | |
| | 1- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 2- BEDROOM EGRESS WINDOW DOESN'T COMPLY WITH THE |
| | MINIMUM CLEAR HEIGHT OPENING REQUIREMENT OF SEC. |
| | R310.2.1 FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | RESPONSE: |
| | SINGLE HUNG WINDOW W3(36"X60") DOESN'T SEEM TO COMPLY |
| | WITH THE MINIMUM CLEAR HEIGHT OPENING REQUIREMENTS OF |
| | SEC. R310.2.1 FBC-RESIDENTIAL. REVISE AS REQUIRED OR |
| | PROVIDE MANUFACTURER'S SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH THE EGRESS HEIGHT REQUIREMENTS. |
| | NOTE: TYPICALLY, 63" HIGH SINGLE HUNG WINDOWS ARE THE |
| | ONES THAT PROVIDE THE 24" CLEAR HEIGHT OPENING. VERIFY |
| | WITH MANUFACTURER. |
| | |
| | 3- OK. |
| | 4- OK. |
| | 5- OK. |
| | 6- OK. |
| | 7- OK. |
| | 8- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | A)ENTRY DOOR FL22513-R3 WAS NOT REVIEWED/APPROVED. |
| | B)SINGLE HUNG WINDOW NOA 20-0401.03 WAS NOT |
| | REVIEWED/APPROVED. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |