Plan Review Notes
Plan Review Notes For Permit 22010353
Permit Number 22010353
Review Stop B
Sequence Number 2
Notes
Date Text
2022-07-05 17:39:29RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010353
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- ENTRY DOOR DOESN'T COMPLY WITH THE MIN. CLEAR WIDTH
 OF 32" AS REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL.
 REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- BEDROOM EGRESS WINDOW DOESN'T COMPLY WITH THE
 MINIMUM CLEAR HEIGHT OPENING REQUIREMENT OF SEC.
 R310.2.1 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR
 VAPOR BARRIER. ARCHITECT OF RECORD TO PROVIDE
 SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS
 REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 4- EXTERIOR WALL: NEED TO SPECIFY TWO LAYERS OF WATER
 RESISTIVE BARRIERS AS REQUIRED BY SEC. SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- ARCHITECT TO REVISE DESCRIPTION OF WORK ON SHEET
 G001. THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE (SEC. 605 FBC FBC-EXISTING BUILDING). AND THIS IS
 ALTERATION LEVEL 3 (SEC. 604 FBC FBC-EXISTING BUILDING)
 NOT ALTERATION LEVEL 2.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- REVISE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS.
 REVISE STRUCTURAL BUCK SIZE. STRUCTURAL BUCK NEEDS TO
 PROVIDE FULL SUPPORT TO THE DOOR FRAME AS REQUIRED BY
 SEC. R609.7.2.1 FBC-RESIDENTIAL. ALSO, BEVELED BUCKS
 ARE NOT LONGER ALLOWED. REVISE ALL DETAILS AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 7- NO SURE IF ROOF SHINGLES ARE GOING TO BE REPLACED OR
 NOT. EXTERIOR ELEVATIONS SAY NO CHANGES BUT
 CONTRACTOR'S CONTRACT SUBMITTED INCLUDE ROOFING.
 CLARIFY AS REQUIRED.
 IF REPLACING ROOF SHINGLES, THEN ARCHITECT OF RECORD
 NEEDS TO SPECIFY HOW COMPLYING WITH THE NEW 2020 CODE
 REQUIREMENT FOR ROOFING UNDERLAYMENT. SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 ROOFING SUB-PERMIT IS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) ROOF SHINGLES ( IF REPLACED)
 B) ROOFING UNDERLAYMENT SPECIFIED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 8- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,