2022-03-25 17:39:26ROOFING REVIEW:
  
 1- NO SURE IF ROOF SHINGLES ARE GOING TO BE REPLACED OR
 NOT. EXTERIOR ELEVATIONS SAY NO CHANGES BUT
 CONTRACTOR'S CONTRACT SUBMITTED INCLUDE ROOFING.
 CLARIFY AS REQUIRED.
 IF REPLACING ROOF SHINGLES, THEN NEED TO SPECIFY HOW
 COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT. SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 ROOFING SUB-PERMIT IS REQUIRED.
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) ROOF SHINGLES ( IF REPLACED)
 B) ROOFING UNDERLAYMENT SPECIFIED.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THOSE ALREADY SUBMITTED) AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]