| 2022-02-17 11:48:19 | ELECTRIC REVIEW FAILED |
| | 1) SERVICE DISCONNECTS MUST BE GROUPED. PLEASE DETAIL |
| | LOCATIONS, ON A SITE PLAN, OF ALL SERVICE EQUIPMENT FOR |
| | MAIN HOUSE AND COTTAGE TO ENSURE COMPLIANCE. NEC |
| | 230.72, FBC 107.2 |
| | 2) SERVICE RISER DETAILS AN EQUIPMENT GROUNDING |
| | CONDUCTOR PARALLELING THE GROUNDED CONDUCTOR FROM METER |
| | TO EACH SERVICE DISCONNECT. PLEASE COMPLY WITH NEC |
| | 250.30(A)(1) SYSTEM BONDING JUMPER |
| | 3) RISER DIAGRAM PANEL LABELING CONFLICTS WITH LABELS |
| | FOR LOAD CALCULATION AND SCHEDULE. PLEASE CORRECT. FBC |
| | 107.2 |
| | 4) SEPARATE STRUCTURE REQUIRE DISCONNECT AT NEAREST |
| | POINT OF ENTRY OF FEEDER CONDUCTORS. NEC 225.32. PLEASE |
| | LOCATE THIS DISCONNECT ON SITE PLAN |
| | 5) PROVIDE GROUNDING ELECTRODE CONDUCTOR FROM 125-AMP |
| | MAIN DISCONNECT. NEC 264(D). PLEASE DETAIL ON PLANS |
| | 6) PROVIDE SEPARATE GROUNDING ELECTRODE SYSTEM AT ANY |
| | REMOTE BUILDINGS FROM SERVICE. NEC 250.32 PLEASE DETAIL |
| | ON RISER DIAGRAM |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |