2022-02-17 11:48:19ELECTRIC REVIEW FAILED
 1) SERVICE DISCONNECTS MUST BE GROUPED. PLEASE DETAIL
 LOCATIONS, ON A SITE PLAN, OF ALL SERVICE EQUIPMENT FOR
 MAIN HOUSE AND COTTAGE TO ENSURE COMPLIANCE. NEC
 230.72, FBC 107.2
 2) SERVICE RISER DETAILS AN EQUIPMENT GROUNDING
 CONDUCTOR PARALLELING THE GROUNDED CONDUCTOR FROM METER
 TO EACH SERVICE DISCONNECT. PLEASE COMPLY WITH NEC
 250.30(A)(1) SYSTEM BONDING JUMPER
 3) RISER DIAGRAM PANEL LABELING CONFLICTS WITH LABELS
 FOR LOAD CALCULATION AND SCHEDULE. PLEASE CORRECT. FBC
 107.2
 4) SEPARATE STRUCTURE REQUIRE DISCONNECT AT NEAREST
 POINT OF ENTRY OF FEEDER CONDUCTORS. NEC 225.32. PLEASE
 LOCATE THIS DISCONNECT ON SITE PLAN
 5) PROVIDE GROUNDING ELECTRODE CONDUCTOR FROM 125-AMP
 MAIN DISCONNECT. NEC 264(D). PLEASE DETAIL ON PLANS
 6) PROVIDE SEPARATE GROUNDING ELECTRODE SYSTEM AT ANY
 REMOTE BUILDINGS FROM SERVICE. NEC 250.32 PLEASE DETAIL
 ON RISER DIAGRAM
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]