| Plan Review Notes For Permit 22010326 |
| Permit Number |
22010326 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-22 16:14:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- SPECIFY CONNECTOR AT: | | | A)(2)1-3/4"X12" LLV BEAM TO (4)2X4 COLUMN. | | | B) TOP AND BOTTOM OF ALL COLUMNS SPECIFIED ON PLANS. | | | C) ROOF FRAMING CONVENTIONAL FRAMING. SPECIFY CONNECTOR | | | AT THE END OF EACH 2X6 ROOF JOIST FRAMING MEMBER. | | | 2- DECORATIVE ROOF @ REAR DOOR DETAIL: SPECIFY | | | CONNECTORS AT EACH FRAMING MEMBER. | | | 3- PRODUCT APPROVALS DEFERRED SUBMITTAL: | | | A)ROOF TILE ADHESIVE LISTED ON THE CLAY ROOF TILE NOA | | | SUBMITTED. | | | B)CLAY TILE NOA SUBMITTED: CLEARLY MARK PADDY SIZE TO | | | BE USED. | | | C)HIP AND RIDGE INSTALLATION. AND, CLEARLY MARK WHICH | | | ONE USED. | | | 4- ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS. |
|