| Plan Review Notes For Permit 22010317 |
| Permit Number |
22010317 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-02-15 15:19:52 | RAILING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) DRAWINGS AND CALCULATIONS SHOW THE DESIGN WIND SPEED | | | AT 160MPH FOR RISK CATEGORY II - RISK GATEGORY II | | | MINIMUM WIND DESIGN SPEED NEEDS TO BE 170 MPH PER FBC | | | WPB SECTION 120. | | | | | | 2) DRAWING 1 OF 3 NOTE NUMBER 4 IS FOR FABRIC - PLEASE | | | CLARIFY. | | | | | | 3) PLEASE SHOW STAIR HANDRAIL EXTENSIONS AT TOP AND | | | BOTTOM OF THE STAIRS PER FBC 1014.6 HANDRAIL | | | EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE | | | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS | | | WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE | | | HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING | | | 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF | | | RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE | | | SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS | | | AND THE RAMP RUNS AT RAMPS. | | | | | | |
|