Plan Review Notes
Plan Review Notes For Permit 22010317
Permit Number 22010317
Review Stop B
Sequence Number 1
Notes
Date Text
2022-02-04 12:34:14RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DRAWINGS AND CALCULATIONS SHOW THE DESIGN WIND SPEED
 AT 160MPH FOR RISK CATEGORY II - RISK GATEGORY II
 MINIMUM WIND DESIGN SPEED NEEDS TO BE 170 MPH PER FBC
 WPB SECTION 120.
  
 2) DRAWING 1 OF 3 NOTE NUMBER 4 IS FOR FABRIC - PLEASE
 CLARIFY.
  
 3) PLEASE SHOW STAIR HANDRAIL EXTENSIONS AT TOP AND
 BOTTOM OF THE STAIRS PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS
 WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS
 AND THE RAMP RUNS AT RAMPS.
  
 4) PLEASE PROVIDE A DRAWING TO SHOW THE LOCATION OF THE
 RAILING TO BE REPLACED. FLOOR PLAN OR ELEVATION PLAN.
  
 5) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 FENCE.