Plan Review Notes
Plan Review Notes For Permit 22010298
Permit Number 22010298
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-26 08:36:18SHEET M.1: THE DRYER EXHAUST DETAIL IS SPECIFYINGA BIRD
 SCREEN AT THE TERMINATION LOCATION. THIS IS NOT ALLOWED
 AND MUST BE REMOVED FROM THE DRAWING. FMC M1502.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved