Plan Review Notes
Plan Review Notes For Permit 22010284
Permit Number 22010284
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-12 10:46:0001/12/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET A-2, A-3, LS-1;
  
 A. THE 30 X 48 IN. CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAIN NEEDS TO BE A FORWARD APPROACH TO THE
 WHEELCHAIR PER THE 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE.
  
 B. ON THE OPEN LAV, WOULD YOU PLEASE SHOW THE SHOW
 CLEAR FLOOR SPACE AND DIMENSION FOR A FORWARD APPROACH,
 AND IT SHALL COMPLY PER THE 2020 FBC ACC SEC. 602.2.
  
 C. ON THE SHOWER, IT SEEMS TO BE A TRANSFER SHOWER, AND
 THE DIMENSION NEEDS TO BE 36 INCHES BY 36 INCHES CLEAR
 INSIDE PER THE 2020 FBC SEC. 608.2.1 TRANSFER TYPE
 SHOWER COMPARTMENTS. WOULD YOU PLEASE SHOW AS WELL THE
 CLEARANCE OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG
 MINIMUM MEASURED FROM THE CONTROL WALL SHALL BE
 PROVIDED?
  
 D. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 2. ON SHEET A-5;
  
 A. UNDER BATHROOM ACCESSORY DETAIL, THE REFLECTIVE PART
 OF THE MIRROR NEEDS TO BE 40" TO THE REFLECTIVE SIDE
 PER THE 2020 FBC ACC SEC. 603.3.
  
 B. THE HORIZONTAL GRAB BARS ON THE REAR NEED TO BE
 MEASURED TO THE CENTER OF THE WATER CLOSET TO 12 INCHES
 TO THE WALL AND 24 INCHES TO THE OPEN SIDE PER THE
 604.5.1 SIDE WALL AND 604.5.2 REAR WALL.
  
 C. THE DRINKING FOUNTAIN SAYS 34 1/2 INCHES, AND THE
 1/2 INCHES EXCEEDS THE MINIMUM HEIGHT PER THE 2020 FBC
 ACCESSIBILITY CODE.
  
 3. ON SHEET P-1;
  
 A. PLEASE PROVIDE A PLUMBING ISOMETRIC RISER DIAGRAM
 FOR SANITARY AND WATER LINES PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 B. FOR THE LAVS, WOULD YOU PLEASE PROVIDE TEMPERED
 WATER THAT SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 AND SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF 110?
 F PER THE 2020 FBC SEC 607.1.2 TEMPERED WATER
 TEMPERATURE CONTROL.
  
 4. SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, AND THE SPACING
 OF THE DOWELS IN THE CENTER. THE REPAIR SHALL ALSO
 INCLUDE TERMITE TREATMENT OF THE SOIL AND THE REQUIRED
 VAPOR BARRIER OVER THE SOIL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  