| 2022-03-09 06:38:53 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22010260 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THERE ARE 2 ENERGY CALCULATIONS SUBMITTED FOR THIS |
| | JOB. ONE IS DATED 12/06/2021 AND ONE IS DATED |
| | 01/06/2022. THEY ARE TOTALLY DIFFERENT AS THE SQUARE |
| | FOOTAGE AND MECHANICAL SYSTEM SIZING ARE DIFFERENT FOR |
| | EACH DOCUMENT. PLEASE LET US KNOW WHICH DOCUMENT YOU |
| | NEED FOR US TO LOCK OUT IN THE SYSTEM. FBC 107.2.1 |
| | |
| | 2) PLEASE SHOW THE RETURN AIR PATH FROM THE 1ST FLOOR |
| | OFFICE BACK TO THE AHU WHEN THE POCKET DOORS ARE |
| | CLOSED. FBC RES M1602.3 |
| | |
| | 3) PLEASE MAKE SURE THAT THE MECHANICAL EQUIPMENT SIZES |
| | MATCH THE MECHANICAL EQUIPMENT SIZING CALCULATIONS THAT |
| | IS CHOSEN FOR THIS PROJECT. FBC EC R403.7.1.2.1 |
| | |
| | 4) THE DESIGNER OF THE MECHANICAL DRAWING MUST PRINT |
| | AND SIGN THEIR NAME IN THE TITLE BLOCK OF THE DOCUMENT. |
| | WPB AMENDMENT 107.2.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |