| 2022-04-14 16:23:38 | PLAN REVIEW BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | BU1635 BN4338 |
| | ASFPM CFM US-21-11935 |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THERE ARE TWO ENERGY SUBMITTALS SUBMITTED FOR |
| | REVIEW. REMOVE ONE AND LEAVE THE ONE YOU WANT REVIEWED. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 2..DESIGNER SHALL PLACE THE CEILING AND WALL INSULATION |
| | R-VALUE ON PLANS. |
| | R402.1.2INSULATION AND FENESTRATION CRITERIA. |
| | THE BUILDING THERMAL ENVELOPE SHALL MEET THE |
| | REQUIREMENTS OF TABLE R402.1.2, BASED ON THE CLIMATE |
| | ZONE SPECIFIED IN CHAPTER 3. |
| | |
| | 3. PROVIDE THE FLORIDA PRODUCT APPROVAL OR UL DESIGN |
| | FOR THE PROPOSED ROOF HATCH. |
| | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL |
| | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE |
| | PROPOSED ROOF HATCH. |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 4. IDENTIFY THE WINOW AND DOOR TYPE ON THE PLANS. PLACE |
| | IT NEXT TO EACH OPENING AND COORDINATE WITH THE WINDOW |
| | AND DOOR SCHEDULE. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE |
| | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES. |
| | R301.2.1.1WIND DESIGN REQUIRED. |
| | |
| | 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER |
| | CALCULATED DESIGN PRESSURES. |
| | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| | SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |