| Plan Review Notes For Permit 22010238 |
| Permit Number |
22010238 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-04-05 09:14:07 | PLAN | | | REVIEW COMMENTS | | | BEACHSIDE POOL | | | | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) COMPLIED. | | | | | | 2) COMPLIED. | | | | | | 3) NOT COMPLIED. [ THE RESPONSE LETTER STATES THAT THE | | | POOL EQUIPMENT IS LOCATED IN THE PARKING GARAGE. THE | | | PLANS SHOW THE POOL EQUIPMENT LOCATED TO THE SOUTH EAST | | | OF THE BEACH CLUB.] THE POOL IS LOCATED IN A SPECIAL | | | FLOOD HAZARD AREA. SHOW HOW THE POOL AND POOL EQUIPMENT | | | WILL COMPLY WITH FBC 1612.4.2. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) NOT COMPLIED. [ THE RESPONSE LETTER STATES THAT THE | | | POOL EQUIPMENT IS TO BE ANCHORED PER THE MANUFACTURER | | | INSTALLATION INSTRUCTIONS. THE MANUFACTURER DOES NOT | | | SPECIFIY ANCHORING FOR WINDLOADS. IF THE EQUIPMENT IS | | | LOCATED INSIDE OF A BUILDING, THE EQUIPMENT DOES NOT | | | HAVE TO BE ANCHORED TO RESIST WIND LOADS.] SHOW HOW THE | | | POOL EQUIPMENT IS ANCHORED TO RESIST WIND LOADS. FBC | | | 1601.1 AND 1603.1.4 | | | | | | 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | |
|