| Date |
Text |
| 2022-12-01 15:58:38 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22010237 |
| | 12/1/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COURTYARD POOL REVIEW COMMENTS. |
| | |
| | 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA |
| | BATHROOMS. |
| | |
| | A) REFER TO SEC. 403.6.1 FBC P: POOL BATHROOMS FOR |
| | FEMALE USE SHALL HAVE A RATIO OF THREE TO TWO WATER |
| | CLOSETS PROVIDED AS THE COMBINED TOTAL OF WATER CLOSETS |
| | AND URINALS PROVIDED FOR MALE USE. |
| | |
| | B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| | SHALL CONTAIN A DIAPER CHANGING STATION- SEC. |
| | 454.1.6.1.1. |
| | |
| | C) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| | SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3. |
| | |
| | D) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25 |
| | FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE |
| | EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4. |
| | |
| | E) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR |
| | INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND |
| | THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR |
| | OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP |
| | RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE |
| | FLOOR DRAINS IN THE BATHROOMS. |
| | |
| | 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE |
| | REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE |
| | POOL DECK- SEC. 454.1.3.1.5 FBC B. |
| | |
| | 3) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE POTABLE WATER |
| | RUNS FROM THE WATER SOURCE TO THE COLLECTOR TANKS AND |
| | LOCATIONS OF POTABLE WATER BACKFLOW PREVENTERS- SEC. |
| | 107.2.1 WPB AND SEC. 454.1.6.3 FBC B |
| | |
| | 4) 2ND REQUEST. PL0.24 &PL0.26: SHOW THE GAS PIPING |
| | RUNS FROM THE GAS SOURCE TO THE POOL HEATERS AND ALL |
| | OTHER GAS FIRED EQUIPMENT OR APPLIANCES. PLEASE PLACE A |
| | NOTE TO INDICATE THE GAS POOL HEATERS AND GAS PIPING |
| | SHALL BE INSTALLED UNDER A SEPARATE PERMIT. |
| | |
| | 5) PL3.21: THE REQUIRED HYDROSTATIC RELIEF VALVE (ITEM |
| | #7) IS NOT SHOWN IN THE DETAIL- SEC. 454.1.6.5.10.4 FBC |
| | B. |
| | |
| | 6) 2ND REQUEST- PL3.11: SHOW GUTTER DRAIN SPACING |
| | DIMENSIONS- SEC. 454.1.6.5.3.1 FBC B. PLEASE NOTE THE |
| | DEPTH MARKING OF 3'0" AT THE SUNSHELF ON PL3.11 & |
| | PL3.10 NEEDS TO BE CHANGED TO SHOW 8". |
| | |
| | 7) DEFERRED SUBMITTALS: ALL POOL AND SPA RECIRCULATION |
| | EQUIPMENT SHALL BE DEFERRED SUBMITTALS WHICH SHALL BE |
| | ONSITE AT TIME OF INSPECTION- SEC. 107.3.4.1 WPB.. EACH |
| | SUBMITTAL SHALL BEAR THE APPROVAL STAMP OF THE ENGINEER |
| | OF RECORD. THE SUBMITTALS SHALL INCLUDE BUT NOT BE |
| | LIMITED TO: |
| | |
| | A) PUMPS. |
| | |
| | B) MAIN DRAIN ASSEMBLIES INCLUDING FRAMES, COVERS, AND |
| | SUMPS. |
| | |
| | C) COLLECTOR TANKS |
| | |
| | D) FILTERS |
| | |
| | E) SKIMMERS |
| | |
| | F) EQUALIZER FITTINGS |
| | |
| | G) HYDROSTATIC RELIEF VALVES |
| | |
| | H) CHLORINATION AND DECHLORINATION EQUIPMENT |
| | |
| | I) ADA LIFTS |
| | |
| | J) EMERGENCY SHOWER AND EYE WASH STATIONS |
| | |
| | |
| | NORTH AND SOUTH SPA REVIEW COMMENTS. |
| | |
| | 1) SHEET PL0.20 COURTYARD POOL, NORTH & SOUTH SPA |
| | BATHROOMS: IN RESPONSE TO 1ST REVIEW COMMENT #1, AN |
| | UPDATED SHEET PL0.20 HAS BEEN PROVIDED WHICH SHOWS THE |
| | LOCATIONS OF THE POOL AND SPA BATHROOMS IN AN ADJACENT |
| | BUILDING WITH A TRAVEL DISTANCE EXCEEDING THE ALLOWABLE |
| | 50 FT. PER SEC. 454.1.6.1.2 FBC B. THE LOCATIONS ARE |
| | LIMITED TO 50 FT. BECAUSE THE RESTROOM DOORS DO NOT |
| | OPEN DIRECTLY TO THE OUTSIDE. DIRECTIONAL SIGNS WOULD |
| | ALSO BE REQUIRED TO BE POSTED WITH DIRECTIONS LEGIBLE |
| | FROM ANY PORTION OF THE POOL DECK. |
| | |
| | A) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| | SHALL CONTAIN A DIAPER CHANGING STATION- SEC. |
| | 454.1.6.1.1. |
| | |
| | B) PROVIDE A DETAIL OR NOTE TO CONFIRM EACH BATHROOM |
| | SHALL CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3. |
| | |
| | C) SHOW THE LOCATIONS OF REQUIRED HOSE BIBS WITHIN 25 |
| | FT. OF EACH BATHROOM AND NOTE THAT EACH WILL BE |
| | EQUIPPED WITH A VACUUM BREAKER- SEC. 454.1.6.1.4. |
| | |
| | D) CONFIRM WITH DETAILS AND/OR NOTES THAT THE FLOOR |
| | INSIDE THE HALLWAY LEADING TO THE POOL BATHROOMS AND |
| | THE POOL BATHROOM FLOORS ARE CONSTRUCTED OF CONCRETE OR |
| | OTHER NON-ABSORBENT MATERIALS AND HAVE A SMOOTH, SLIP |
| | RESISTANT FINISH. INDICATE THE FLOORS SLOPE TO THE |
| | FLOOR DRAINS IN THE BATHROOMS |
| | |
| | 2) 2ND REQUEST. PL0.20: SHOW THE LOCATION OF THE |
| | REQUIRE HOSE BIB OR BIBS WITH VACUUM BREAKERS FOR THE |
| | POOL AND SPA DECK- SEC. 454.1.3.1.5 FBC B. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |