| Plan Review Notes For Permit 22010230 |
| Permit Number |
22010230 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-10 15:27:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE VOLTAGE CALCULATION | | | SHEET OF THE SEPARATE BATTERY CALCULATION UNDER THE | | | NUMBER OF DEVICES FOR THE VARIOUS NAC OUPUTS OF ONLY 1 | | | DEVICE ON EACH OUTPUT. | | | | | | THE RISER DIAGRAM INDICATES NUMEROUS DEVICES ON EACH | | | NAC. | | | | | | FOR THE OFFICIAL RECORD, PLEASE REVIEW AND CORRECT OR | | | PROVIDE A DETAILED EXPLANATION. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|