| Date |
Text |
| 2022-06-24 19:56:01 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING AUDIT |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22010192 |
| | |
| | 1- OK. |
| | 2- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | A)REPORT SUBMITTED HAS THE WRONG ADDRESS. THIS ADDRESS |
| | IS 2441 MEDINA WAY NOT 2717 MEDINA WAY. REVISE AS |
| | REQUIRED. |
| | |
| | B)REPORT IS A PRELIMINARY REPORT AND IS INCONCLUSIVE. |
| | NEED FINAL REPORT WITH LAND PREPARATION AND FOOTING |
| | RECOMMENDATION. |
| | |
| | C)REPORT SUBMITTED HAS A COPY OF THE ENGINEER |
| | SEAL/SIGNATURE. EITHER SUBMIT REPORT ELECTRONICALLY |
| | WITH A VERIFIABLE DIGITAL SIGNATURE OR PROVIDE HARD |
| | COPY WITH ORIGINAL SEAL/SIGNATURE AS REQUIRED BY SEC. |
| | 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING |
| | PLANS/DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | ORIGINAL COMMENT: |
| | 4- NEED BATHROOM ON THE FIRST FLOOR WITH MAXIMUM |
| | POSSIBLE PRIVACY AND A DOOR THAT PROVIDES 29" MIN. |
| | CLEAR OPENING AS REQUIRED BY SEC. R320.1.1 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | RESPONSE LETTER STATES "PLEASE SEE REVISED PLAN A/1.01 |
| | FOR DOOR #107A, SHOWN AS 2'-10 WIDE". DOOR #107A |
| | CORRESPONDS TO THE POWDER ROOM. |
| | THERE ARE COMPLETE BATHROOMS ON THE FIRST FLOOR. NEED A |
| | COMPLETE BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A |
| | DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED |
| | BY SEC. R320.1.1 FBC-RESIDENTIAL. |
| | ALSO, INTERIOR DOORS $ CASED OPENINGS SCHEDULE ON SHEET |
| | A7.02 SPECIFIES DOOR #107A WITH 2'-8" WIDE DOOR NOT |
| | 2'-10" AS SPECIFIED ON THE RESPONSE LETTER. |
| | |
| | 5- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 6- PLANS DON'T PROVIDE DETAILS AND SPECIFICATIONS FOR |
| | THE CONSTRUCTION OF BALCONY GUARDRAILS SHOWING |
| | COMPLIANCE WITH THE REQUIREMENTS OF SEC. R312.1 |
| | FBC-RESIDENTIAL AND TABLE R301.5 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | DESIGNER OF RECORD NEEDS TO PROVIDE THE DETAIL AND |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF THE GUARDRAILS |
| | AS REQUIRED BY TABLE R301.5, SEC. R311.7.8 AND SEC. |
| | R312.1 FBC-RESIDENTIAL. SUBSEQUENT SHOP DRAWINGS ARE TO |
| | CONFIRM THAT DESIGN DETAILS AND SPECIFICATIONS ARE MET. |
| | |
| | ORIGINAL COMMENT: |
| | 7- PLANS DON'T PROVIDE DETAILS AND SPECIFICATIONS FOR |
| | THE CONSTRUCTION OF THE TERRACOTTA BARREL TILE BALCONY |
| | GUARDRAILS SHOWING COMPLIANCE WITH THE REQUIREMENTS OF |
| | SEC. R312.1 FBC-RESIDENTIAL AND TABLE R301.5 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SEE RESPONSE FOR ITEM #6 ABOVE. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 8- NEED TO SPECIFY ATTIC ACCESSS SIZE AND LOCATION IN |
| | MASTER BEDROOM WING SHOWING COMPLIANCE WITH SEC. R807 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | SIZE OF ATTIC ACCESS DOESN'T COMPLY WITH THE ROUGH |
| | OPENING REQUIRED. |
| | NOTE: IN ORDER TO AVOID CONFLICTS/DELAYS PLEASE VERIFY |
| | ATTIC ACCESS PROPOSED LOCATION. IT LOOKS LIKE IT MAY |
| | NOT HAVE READY ACCES WITH THE CLOSET SHELVES BELOW IT. |
| | ALSO, THERE MAY NO BE ENOUGH HEADROOM AT THE ATTIC TO |
| | ACCESS MASTER BEDROOM AREA. |
| | |
| | 9- OK. |
| | 10-OK. |
| | 11-OK. |
| | |
| | 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | |
| | A)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | RESPONSE: |
| | WILL BE A DEFERRED SUBMITTAL. |
| | NOTE: CUSTOM DOOR WILL NEED A COMPLETE SITE SPECIFIC |
| | PRODUCT APPROVAL ENGINEERING ANALYSIS FOR BUILDING |
| | OFFICIAL APPROVAL. SIGNED AND SEALED. |
| | |
| | B)OK. |
| | |
| | C)FIXED WINDOW TYPE "C" AS SHOWN ON PLANS. |
| | RESPONSE: |
| | PRODUCT APPROVAL SUBMITTED DOESN'T COVER FIXED WINDOW |
| | TYPE "C" CONFIGURATION SHOWN ON PLANS. |
| | |
| | D)OK. |
| | E)OK. |
| | F)OK. |
| | G)OK. |
| | |
| | D) ROOF TILE ADHESIVE LISTED ON THE ROOF TILE NOA AND |
| | SPECIFY PADDY SIZE. |
| | RESPONSE: |
| | NOT SUBMITTED. |
| | |
| | 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 14- OK. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| | REVISION MADE WILL HELP TO EXPEDITE THE AUDIT PROCESS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |