| Plan Review Notes For Permit 22010192 |
| Permit Number |
22010192 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-20 17:35:04 | ROOFING AUDIT: | | | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | A) ROOFING UNDERLAYMENT SPECIFIED ON PLANS. AND, | | | CLEARLY SPECIFY SELECTED ASSEMBLY TO BE INSTALLED. | | | | | | B) HIP & RIDGE METAL SUPPORT TO BE USED FOR ROOF TILES. | | | | | | C) ROOF TILE NOA SUBMITTED: CLEARLY SPECIFY ADHESIVE | | | PARTY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING | | | PERMITS TO VERIFY UPLIFT. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | D) ROOF TILE ADHESIVE LISTED ON THE ROOF TILE NOA AND | | | SPECIFY PADDY SIZE. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] |
|