| Plan Review Notes For Permit 22010157 |
| Permit Number |
22010157 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2022-04-06 13:58:11 | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE | | | BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING | | | COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | | PRIOR TO ANY INSTALLATION. | | | | | | ALL WORK ON THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE | | | COMPLETED BY A CERTIFIED FIRE SPRINKLER CONTRACTOR AND | | | SHALL COMPLY WITH NFPA 13. SEPARATE SHOP DRAWINGS, ARE | | | REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY THE | | | FIRE PREVENTION BUREAU PRIOR TO ANY WORK ON THE SYSTEM. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|