| 2022-01-07 08:27:23 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL2533-R24 HAS BEEN |
| | REVISED TO FL2533-R26. PLEASE PROVIDE A COMPLETE SET. |
| | INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL2533-R24 SELECTED SYSTEM NO. W-65 DO NOT |
| | MEET THE EXPOSURE CATEGORY C; ZONE 3 MINIMUM DESIGN |
| | PRESSURE REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM |
| | NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR |
| | ZONE 3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |