| Plan Review Notes For Permit 22010139 |
| Permit Number |
22010139 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-07 11:56:50 | 1ST REVIEW FBC-2020 RES. | | | PERMIT- 22010139 | | | 1/7/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-01 & P-02: BATH #3 WET VENTING IS NOT IN | | | COMPLIANCE WITH SECS. P3108.1 & P3108.2.1 FBC RES. THE | | | BAR SINK IS NOT A BATHROOM FIXTURE AND THE DRAIN SHALL | | | NOT CONNECT TO THE WET VENT. THE DRY VENT FOR THE | | | SYSTEM SHALL BE AN INDIVIDUAL OR COMMON VENT FOR A | | | BATHROOM FIXTURE AND NOT A CLEAN-OUT. | | | | | | 2) P-01 & P-02: THE 2-INCH WASHING MACHINE FIXTURE | | | DRAIN SHALL CONNECT TO A 3-INCH VERTICAL STACK- A | | | 2-INCH STACK IS SHOWN- SEC. 406.2 FBC P. | | | | | | 3) P-01: REFER TO SEC. R305.1 AND PROVIDE A DIMENSIONED | | | ELEVATION DETAIL VIEW OF THE POWDER ROOM WATER CLOSET | | | UNDERNEATH THE STAIRS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|