Plan Review Notes
Plan Review Notes For Permit 22010139
Permit Number 22010139
Review Stop P
Sequence Number 1
Notes
Date Text
2022-01-07 11:56:501ST REVIEW FBC-2020 RES.
 PERMIT- 22010139
 1/7/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-01 & P-02: BATH #3 WET VENTING IS NOT IN
 COMPLIANCE WITH SECS. P3108.1 & P3108.2.1 FBC RES. THE
 BAR SINK IS NOT A BATHROOM FIXTURE AND THE DRAIN SHALL
 NOT CONNECT TO THE WET VENT. THE DRY VENT FOR THE
 SYSTEM SHALL BE AN INDIVIDUAL OR COMMON VENT FOR A
 BATHROOM FIXTURE AND NOT A CLEAN-OUT.
  
 2) P-01 & P-02: THE 2-INCH WASHING MACHINE FIXTURE
 DRAIN SHALL CONNECT TO A 3-INCH VERTICAL STACK- A
 2-INCH STACK IS SHOWN- SEC. 406.2 FBC P.
  
 3) P-01: REFER TO SEC. R305.1 AND PROVIDE A DIMENSIONED
 ELEVATION DETAIL VIEW OF THE POWDER ROOM WATER CLOSET
 UNDERNEATH THE STAIRS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  