2022-01-15 08:05:08ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD CALCULATION IS HARD TO FOLLOW, PLEASE SEE
 EXAMPLES IN ANNEX D OF THE NEC FOR LAYOUT OF LOAD
 CALCULATION. 220
  
 2) SUBFEED TO POOL HAS #8 CONDUCTOR ON A 60 AMPERE
 BREAKER.