| Plan Review Notes For Permit 22010139 |
| Permit Number |
22010139 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-15 08:05:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) LOAD CALCULATION IS HARD TO FOLLOW, PLEASE SEE | | | EXAMPLES IN ANNEX D OF THE NEC FOR LAYOUT OF LOAD | | | CALCULATION. 220 | | | | | | 2) SUBFEED TO POOL HAS #8 CONDUCTOR ON A 60 AMPERE | | | BREAKER. |
|