| 2022-03-08 09:42:52 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | BU1635 BN4338 |
| | ASFPM CFM US-21-11935 |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | NOTICE: APPROX. 328 SF OF CONCRETE PATIO PROPOSED: |
| | |
| | 1. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| | IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| | INCLUDED BOUNDARY LINE SURVEY. |
| | FBC R401.3 SITE DRAINAGE |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. |
| | LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| | FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| | INCHES WITHIN THE FIRST 10 FEET. |
| | |
| | 2.PROVIDE AN ENERGY SUBMITTAL (EXEMPT PER FBC EXISTING |
| | R501.6 HISTORIC BUILDING) CT |
| | |
| | 3. PROVIDE A COPY OF THE ICC-ES REPORT FOR THE SPRAY |
| | FOAM INSULATION. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. PRODUCT APPROVALS FL15976, 22250 & 22551 HAVE |
| | EXPIRED. |
| | PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL |
| | OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 FBC, FOR THE |
| | PROPOSED WINDOW MULLIONS TO BE INSTALLED. |
| | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| | |
| | 5.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE |
| | R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES |
| | R301.2.1.1WIND DESIGN REQUIRED. |
| | |
| | 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN |
| | PRESSURES. |
| | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| | SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |
| | |
| | |
| | |
| | |