| Plan Review Notes For Permit 22010130 |
| Permit Number |
22010130 |
|
| Review Stop |
NFIP |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-18 14:20:38 | ELEVATION CERTIFICATE PEER REVIEW | | | STATUS IS DENIED | | | | | | 1) THE INFORMATION ON THE ELEVATION CERTIFICATE DOES | | | NOT MATCH THE PLANS FOR THE HOUSE. THE PHOTOS THAT WERE | | | SUBMITTED WITH THE ELEVATION CERTIFICATE SHOW TWO | | | ENGINEERED SMART VENTS IN EACH OF THE TWO OVERHEAD | | | GARAGE DOORS LOCATED ON THE NORTH WALL FOR A TOTAL OF | | | FOUR. THERE ARE TWO NON-ENGINEERED 36" X 24" FLOOD | | | OPENINGS ON THE EAST GARAGE WALL. REVISE PLAN SHEETS | | | A-1.0 AND A-6.0 TO MATCH WHAT HAS BEEN INSTALLED AND | | | CORRECT THE GARAGE LOUVER CALCULATIONS ON SHEET A1.0 | | | ACCORDINGLY. | | | | | | 2) SUBMIT THE DOCUMENTATION FROM THE MANUFACTURER FOR | | | THE 36" X 24" GREENHECK AF J601X LOUVERS THAT SPECIFIES | | | THE NET FREE OPENING AREA. | | | | | | 3) SUBMIT THE COMPLETE PRODUCT APPROVALS FOR THE GARAGE | | | DOOR SMART VENTS INCLUDING THE EVALUATION REPORT AND | | | INSTALLATION INSTRUCTIONS. | | | | | | 4) THE NOTES IN THE COMMENT SECTION OF THE ELEVATION | | | CERTIFICATE FOR THE FLOOD VENTS SPECIFY NET AREA WHICH | | | IS MISLEADING AS TO BEING THE NET FREE VENT AREA WHEN | | | IT IS ACTUALLY THE GROSS AREA OF THE VENTS. PLEASE | | | CORRECT TO STATE GROSS AREA. | | | |
|