| 2022-03-21 17:11:54 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22010129 |
| | 3/21/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. REMAINING 1ST REVIEW |
| | COMMENTS LISTED BELOW. |
| | |
| | 1) FAILED. SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING |
| | FIXTURE CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC |
| | P. PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY |
| | WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET |
| | C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT |
| | DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY |
| | AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE |
| | REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE |
| | DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE |
| | PROVIDED- SEC.- 410.4 FBC P. THE CORRECTED C-1 SHEET |
| | WAS NOT UPLOADED. |
| | |
| | 3) FAILED. SHEET 1.0A- MISSING ACCESSIBILITY DETAILS |
| | PER FBC ACC: |
| | K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC. |
| | 605.2. NOT PROVIDED. |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE URINAL- SEC. 605.3. NOT PROVIDED. |
| | |
| | 4) FAILED. SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS |
| | OF THE STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P. |
| | NOT PROVIDED. |
| | |
| | |
| | 5) FAILED. SHEET 3.0P: PROVIDE GREASE WASTE |
| | CALCULATIONS IN COMPLIANCE WITH SEC. 1003.3.5 FBC P. |
| | PLEASE ADD THE GREASE INTERCEPTOR TO THE LIST OF |
| | SEPARATE PERMITS ON SHEET C-1. NOTE: COMPLETE GREASE |
| | INTERCEPTOR PLANS, EQUIPMENT SPECIFICATIONS, |
| | CALCULATIONS AND DETAILS WILL BE REQUIRED UNDER THE |
| | SEPARATE PERMIT. CORRECTED SHEET 3.0P NOT UPLOADED. |
| | |
| | 12) FAILED. SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE |
| | PERMIT IS REQUIRED FOR THE POTABLE WATER SERVICE |
| | BACKFLOW PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE |
| | ADD THE DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET |
| | C-1. SHEET C-1 WITH MODIFED SEPARATE PERMIT LIST NOT |
| | UPLOADED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |