| Date |
Text |
| 2022-03-21 17:10:50 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 22010129 |
| | 3/21/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. REMAINING COMMENTS FROM |
| | THE 1ST REVIEW ARE LISTED BELOW. |
| | |
| | 1) FAILED. SHEET 3.0P GAS RISER: INCREASE THE 1-INCH |
| | PIPE SHOWN AT THE 33 FT. RUN TO 1-1/2-INCH BASED ON |
| | TABLE 402.4(2) FBC FG. CORRECTED SHEET 3.0P NOT |
| | UPLOADED. |
| | |
| | 2) FAILED. SHEET 3.0P GAS RISER: SHOW THE BRANCH PIPE |
| | SIZES FOR THE APPLIANCES ON THE COOKING LINE- TABLE |
| | 402.4(2) FBC FG. SHEET 3.1P SHOWS INDIVIDUAL COMBUSTION |
| | AIR INTAKE AND EXHAUST DUCTS. ALL OTHER PLANS INDICATE |
| | A CONCENTRIC VENT- WHICH IS IT? |
| | |
| | 4) FAILED. SHEET 3.0P: PROVIDE A VENTING DIAGRAM FOR |
| | THE TANKLESS WATER HEATER SHOWING THE TYPE AND SIZE OF |
| | CONCENTRIC, VENT RUN LENGTH FROM THE APPLIANCE TO THE |
| | TERMINATION ABOVE THE ROOF, CLEARANCE HEIGHT ABOVE THE |
| | ROOF, AND CLEARANCES TO AIR EXHAUST OUTLET AND AIR |
| | INTAKES ON THE ROOF- SECS. 503.2.3, 503.8 & 624.1. A) |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CONCENTRIC |
| | VENT DUCT- SECS. 503.4.1 & 624.1 FBC FG. PLEASE NOTE |
| | THE VENT DUCT SHALL BE LISTED AND LABELED PER SEC. |
| | 503.3.6: |
| | |
| | WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING |
| | AIR-HANDLING SPACE OR OTHER NON-DUCTED PORTION OF AN |
| | AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM |
| | TO ONE OF THE FOLLOWING REQUIREMENTS: |
| | |
| | 1.THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS |
| | VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR |
| | CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT, |
| | WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR |
| | VENT MANUFACTURER?S INSTRUCTIONS. |
| | 2.THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT |
| | FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED |
| | IN THE ABOVE-CEILING SPACE. |
| | 3.THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT OR |
| | ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR OF |
| | THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE. VENT |
| | SPECS NOT SUBMITTED |
| | |
| | 6) FAILED. SHEET 3.0P: THE PLAN SHOWS A GAS-FIRED |
| | TANKLESS WATER HEATER ON THE EXTERIOR WALL. IS THIS |
| | HEATER IN USE OR TO BE REMOVED- SEC. 107.2.1 WPB. |
| | CORRECTED SHEET 3.0P NOT UPLOADED. |
| | |
| | 7) FAILED. SHEET 3.0P: PROVIDE A CONDENSATE DISPOSAL |
| | PLAN FOR THE NEW INTERIOR GAS-FIRED WATER HEATER- SECS. |
| | 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF |
| | CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN |
| | LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING |
| | DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. CORRECTED |
| | SHEET 3.0P NOT UPLOADED. PLEASE NOTE THAT CONDESNATE |
| | SHALL NOT DRAIN INTO THE SANITARY SYSTEM- SEC. 90-126 |
| | WPB CODE OF ORDINANCES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |