| 2022-01-20 17:43:36 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22010129 |
| | 1/20/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS C-1, 1.3A, 3.0P: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN COMPLIANCE WITH TABLE 403.1 FBC P. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED NUMBER OF PLUMBING FIXTURES. PLEASE CLARIFY |
| | WHICH OCCUPANT LOAD IS CORRECT- (161 OCCUPANTS- SHEET |
| | C-1) OR (178 OCCUPANTS- SHEET 1.3A). PLEASE NOTE THAT |
| | DRINKING FOUNTAINS ARE REQUIRED FIXTURES FOR ASSEMBLY |
| | AND BUSINESS OCCUPANCIES. SHOW THE LOCATION OF THE |
| | REQUIRED DRINKING FOUNTAINS OR PLACE A NOTE TO INDICATE |
| | DRINKING WATER IN A CONTAINER FREE OF CHARGE WILL BE |
| | PROVIDED- SEC.- 410.4 FBC P. |
| | |
| | 2) SHEETS 1.0A, 1.3A, 3.0P, 3.1P: SHEET 1.3A INDICATES |
| | A 1390 SQ. FT. BREWERY. SHOW THE LOCATION OF THE |
| | BREWERY AND PROVIDE AN EQUIPMENT PLAN AND SCHEDULE- |
| | SEC. 107.2.1 WPB. |
| | |
| | 3) SHEET 1.0A- MISSING ACCESSIBILITY DETAILS PER FBC |
| | ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SEC. 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SEC. 606.2. |
| | C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| | WALLS- SEC. 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SEC. 604.4. |
| | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| | FROM THE FINISHED FLOOR- SEC. 606.3. |
| | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SEC. 603.3 |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. |
| | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ? SEC. |
| | 604.6. |
| | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | K) HEIGHT AND DEPTH OF THE ACCESSIBLE URINAL- SEC. |
| | 605.2 |
| | L) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE URINAL- SEC. 605.3. |
| | M) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| | 606.2 |
| | |
| | 4) SHEET 1.0A: PROVIDE THE DEPTH MEASUREMENTS OF THE |
| | STANDARD RESTROOM STALLS- SEC. 405.3.1 FBC P. |
| | |
| | 5) SHEET 3.0P: PROVIDE GREASE WASTE CALCULATIONS IN |
| | COMPLIANCE WITH SEC. 1003.3.5 FBC P. PLEASE ADD THE |
| | GREASE INTERCEPTOR TO THE LIST OF SEPARATE PERMITS ON |
| | SHEET C-1. NOTE: COMPLETE GREASE INTERCEPTOR PLANS, |
| | EQUIPMENT SPECIFICATIONS, CALCULATIONS AND DETAILS WILL |
| | BE REQUIRED UNDER THE SEPARATE PERMIT. |
| | |
| | 6) SHEETS 3.0P & 3.1P: SHOW THE LOCATION OF THE GREASE |
| | INTERCEPTOR SAMPLING PORT AND INDICATE ACCESS WILL BE |
| | PROVIDED TO THE INTERCEPTOR COVERS AND CLEANOUTS- SECS. |
| | 708.1.7 & 708.1.10 FBC P. |
| | |
| | 7) SHEET 3.0P: THE LOCATION OF THE FLOOR SINK IN THE |
| | DETAIL DOES NOT MATCH THE LOCATION ON THE PLAN. THE |
| | PLAN SHOWS THE FLOOR SINK BETWEEN THE FOOD HANDLING |
| | (3-COMPARTMENT) SINK AND THE WARE WASHER- SEC. 802.1.1 |
| | AND 802.3 FBC P. PLEASE INCLUDE THE FLOOR SINKS IN THE |
| | PLUMBING FIXTURE SCHEDULE- SECS. 414.1 & 802.4 FBC P. |
| | |
| | 8) SHEETS 3.0P & 3.1P: PROVIDE VENTS FOR THE FLOOR |
| | SINKS AND FLOOR DRAINS IN THE KITCHEN AREA- SEC. 802.3 |
| | FBC P AND THE FLOOR DRAIN IN THE MEN'S RESTROOM- SECS. |
| | 910 & 911 FBC P. |
| | |
| | 9) SHEETS 3.0P & 3.1P: THE PLAN SHOWS 3/4-INCH SUPPLY |
| | LINES TO THE URINALS, AND THE RISER SHOWS 1-INCH- SEC. |
| | 107.2.1 WPB. PLEASE NOTE A COMPLETE REVIEW OF THE |
| | PLUMBING PLANS CANNOT BE COMPLETED WITH A PLUMBING |
| | FIXTURE SCHEDULE- TABLE 604.5 FBC P. |
| | |
| | 10) SHEETS 3.0P & 3.1P: SHOW LOCATIONS OF REQUIRED |
| | BACKFLOW PREVENTERS FOR SUPPLY LINES CONNECTING TO THE |
| | WARE WASHER, GLASS WASHER, AND ICE MAKERS- SEC. 608.3 |
| | FBC P. |
| | |
| | 11) SHEETS 3.0P & 3.1P: A RECIRCULATION PUMP IS SHOWN |
| | BUT THERE IS A NOTE INDICATING A RECIRCULATING WATER |
| | HEATER. WHICH RECIRCULATION SYSTEM WILL BE USED?- SEC. |
| | 607.1 FBC P. |
| | |
| | 12) SHEETS 3.0P & 3.1P: PLEASE NOTE A SEPARATE PERMIT |
| | IS REQUIRED FOR THE POTABLE WATER SERVICE BACKFLOW |
| | PREVENTER- SEC. 105.1 & 107.2.1 WPB. PLEASE ADD THE |
| | DEVICE TO THE LIST OF SEPARATE PERMITS ON SHEET C-1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |