| 2022-01-13 12:06:48 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-22010129 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE LIFE SAFETY PLAN INDICATES A BREWERY BUT I DO |
| | NOT SEE ONE ON THE DRAWINGS. PLEASE LABEL EACH USE OF |
| | SPACE IN THIS CHANGE OF USE TENANT SPACE. FBC 107.2.1 |
| | |
| | 2) THE LIFE SAFETY SHEET INDICATES THE KITCHEN SQUARE |
| | FOOTAGE AS 1775, SHEET 4.0M INDICATES IN THE OUTDOOR |
| | AIR CALCULATIONS THAT THE KITCHEN SQUARE FOOTAGE IS |
| | ONLY 807. PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 3) THE LIFE SAFETY SHEET INDICATES THE LOUNGE SQUARE |
| | FOOTAGE AS1583, SHEET 4.0M INDICATES IN THE OUTDOOR AIR |
| | CALCULATIONS THAT THE DINING ROOM SQUARE FOOTAGE IS |
| | 2695. PLEASE BE CONSISTENT. FBC 107.2.1 |
| | |
| | 4) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH |
| | USE OF SPACE IN THIS TENANT SPACE ACCORDING TO THE FBC |
| | M 403.3.1.1 AND TABLE 403.3.1.1 AND NOT THE OCCUPANT |
| | COUNT FROM THE ARCHITECT. |
| | |
| | 5) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR EACH UNIT. FBC EC C403.2.1 |
| | |
| | 6) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE DISTRIBUTED |
| | CONSISTENTLY IN THIS TENANT SPACE. FBC 107.2.1 |
| | |
| | 7) PLEASE IDENTIFY THE UNIT IN THE KITCHEN ON THE |
| | MECHANICAL DRAWING. FBC 107.2.1 |
| | |
| | 8) SHEET 2.2E INDICATES THERE IS A DISHWASHER, PLEASE |
| | SHOW THIS DISHWASHER ON THE MECHANICAL DRAWINGS. PLEASE |
| | ALSO PROVIDE DETAILS FOR THIS DISHWASHER. PLEASE SHOW |
| | HOW THIS DISHWASHER MEETS THE REQUIREMENTS OF FBC M |
| | 507.3 FOR HAVING A HOOD ABOVE THE DISHWASHER. |
| | |
| | 9) PLEASE PROVIDE THE CONDENSATE PIPE, SIZE AND |
| | TERMINATION LOCATION. FBC M 307 |
| | |
| | 10) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF WILL |
| | MEET THE GUARDS REQUIREMENT IN FBC M 304.11 |
| | |
| | 11) PLEASE SHOW THAT THE NEW EQUIPMENT ACCESS WILL MEET |
| | THE REQUIREMENTS FOR ACCESS INCLUDING THE 30 INCH HIGH |
| | REQUIREMENT FOR CLIMBING OVER OBSTRUCTIONS. FBC M 306.5 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |