| Plan Review Notes For Permit 22010047 |
| Permit Number |
22010047 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-10 07:45:06 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, IDENTIFY, ON DRAWINGS, THE STRUCTURE | | | THAT WILL BE COVERED UNDER THIS PERMIT. | | | 2.) FBC B 1609, PROVIDE THE ENGINEER SIGNED/SEALED | | | WINDLOAD DESIGN INFORMATION AND THE CALCULATIONS WITH | | | FASTENER SPACING FOR ROOING MATERIALS. | | | 3.) FBC B 107.2.1, PROVIDE A SUB-PERMIT FOR ROOFING | | | WORK. | | | 4.) FBC B 107.2.1, THE "A" SHEETS BY R&R CONSTRUCTION | | | NEED TO BE SIGNED BY THE INDIVIDUAL FROM R&R THAT IS | | | RESPONSIBLE FOR THESE SHEETS. | | | 5.) AN ELECTRICAL SUB-PERMIT IS REQUIRED FOR ELECTRICAL | | | WORK. |
|