| Plan Review Notes For Permit 22010045 |
| Permit Number |
22010045 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-10 09:25:59 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE THE SIGNED/SEALED WINDLOAD | | | DESIGN PRESSURES WITH FASTENER SPACING CALCULATIONS FOR | | | THE ROOFING SYSTEM. | | | 2.) WPB AMENDMENTS OF FBC B 107.2.1, THE "A" SHEETS | | | NEED TO BE SIGNED BY THE INDIVIDUAL WHO DESIGNED THEM | | | FROM R&R CONSTRUCTION. | | | 3.) A ROOFING SUB-PERMIT IS REQUIRED FOR ROOFING WORK. |
|