| Notes |
| Date |
Text |
| 2022-02-04 16:23:17 | FIRE PROVISO: | | | | | | FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED | | | CODE: 603 | | | | | | CITY OF WEST PALM BEACH | | | | | | FIRE SPRINKLER PERMIT # 22010005 | | | | | | TEST @ WORKING PRESSURE FOR 2 HOURS PER | | | NFPA13 | | | | | | CONTRACTOR TO PROVIDE FOR WORKING PRESSURE | | | VERIFICATION (I.E. PRESSURE GAUGE 2HRS) AND/OR | | | SYSTEM IS CHARGED/DISCHARGED UNDER WORKING | | | PRESSURE. (I.E. VISUAL FOR LEAKS & INSPECTOR | | | DRAIN AFTER 2 HRS) | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|