| 2022-04-07 08:31:04 | 04/07/22 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | 1. ON SHEET P101; |
| | |
| | A. THE ARE TWO DIFFERENT SETS OF SYSTEMS ON THIS PAGE, |
| | ONE SHOWS AN LP TANK, AND IT ALSO INDICATES A GAS |
| | METER. WOULD YOU PLEASE CLARIFY BY SHOWING THE SYSTEM |
| | LP OR GAS PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE SEEMS TO BE A NEW LINE FOR THE DRYER AND THE |
| | GENERATOR THAT IS NOT SHOWN IN THE ISOMETRIC GAS RISER. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| | |
| | C. THERE IS A GAS POOL HEATER, AND IT DOES NOT SHOW ANY |
| | GAS LINE TO IT. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1 OR 410.1. |
| | |
| | E. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1 OR 2020 FBC RES. SEC. G2408.1. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE |
| | TIME OF INSPECTION PER THE 2020 FBC RES. SEC. G2413.2 |
| | AND G2404.3 |
| | . |
| | F. THERE IS A GAS TANKLESS SHOWN ON THE ISOMETRIC BUT |
| | NOT SHOWN IN THE FLAT DRAWING. WOULD YOU PLEASE CORRECT |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | G. WOULD YOU PLEASE SHOW ON THE HOUSE PLAN THE LOCATION |
| | OF THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| | DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| | TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| | SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | H. WOULD YOU PLEASE SUBMIT COMBUSTION AIR CALCULATIONS |
| | FOR THE ADDED GAS DRYER APPLIANCES. WHERE DOES THE |
| | BUILDING'S MECHANICAL VENTILATION SYSTEM PROVIDE |
| | COMBUSTION AIR? THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| | COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| | VENTILATION AIR PER THE FBC RES. SEC. G2407.9.3. |
| | COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM. |
| | |
| | I. IF LOUVERS ARE USED, LOUVERS THAT ARE BEING |
| | INSTALLED FOR THE COMBUSTION AIR SHOW THE LOUVERS' |
| | LOCATION. THE LOUVERS CANNOT BE LOCATED ON AN EXTERIOR |
| | WALL THAT IS FIRE RATED AS THE FIRE RATING OF THE WALL |
| | MUST BE MAINTAINED PER THE WPB AMENDMENTS TO FBC |
| | SEC.107.2.1. |
| | |
| | J. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, LABEL ALL PIPE SIZES, AND THE |
| | CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| | STAINLESS-STEEL TUBING (IF APPLICABLE) FOR EACH PIPE |
| | SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | K. WOULD YOU PLEASE SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR PER |
| | THE 2020 FBC RES. SEC. G2420.4. |
| | |
| | L. THE BTU'S LOAD IS INCORRECT. WOULD YOU PLEASE SHOW |
| | THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| | ON THE SYSTEM? REFER TO THE 2020 FBC RES. SEC. G2413. |
| | |
| | M. WOULD YOU PLEASE CORRECT THE DISTANCE FROM THE POINT |
| | OF DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | N. ON THE GAS NOTES, IT REFERS TO THE 2014 FUEL GAS |
| | CODE, AND THE CURRENT IS 2020 FBC 7 EDITION FUEL GAS. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | O. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE PER THE FBC RES. SEC |
| | G2421.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |