| Date |
Text |
| 2022-02-01 12:13:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21121220 4920 LORING DR |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT |
| | LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE |
| | PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY |
| | WITH 606. |
| | |
| | 2. MATERIAL SPEC PER WPB FBC 107.2.1, PROVIDE PIPING |
| | MATERIAL SPEC FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, |
| | FITTINGS AND JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, |
| | 7, 9 AND 11. |
| | |
| | 3. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH |
| | A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON |
| | THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW |
| | SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT |
| | AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR |
| | SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS |
| | WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE |
| | FOR FINAL INSPECTION. |
| | |
| | 5. PER WPB FBC 107.2.1 AND 107.3.5.1.3 , PROVIDE A |
| | SCHEDULE, CALCULATIONS AND DETAIL OF THE GREASE |
| | INTERCEPTOR SHOWING COMPLIANCE WITH FBC PL 1003.3.5 AND |
| | 1003.3.5.1. |
| | |
| | 6. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE THE |
| | FOLLOWING: |
| | ?A) A DETAIL FOR THE SEPARATE DISCHARGES OF THE GREASY |
| | WASTE AND THE DISPOSAL WASTE FROM THE NEW SINK TO |
| | SANITARY; INCLUDE THE DISCHARGE FROM THE DISHWASHER. |
| | ?B) CLEARLY SHOW ON THE SANITARY RISER DIAGRAM TWO |
| | SEPARATE TRAPPED AND VENTED FIXTURE DRAINS FOR THE |
| | DISPOSAL AND FOR SINK/DISHWASHER. |
| | ?C) PROVIDE SIZING FOR ALL NEW DRAINS ON THE SANITARY |
| | RISER DIAGRAM. |
| | |
| | 7. P-2, DEMO NOTE 5 INDICATES AN EXISTING FLOOR DRAIN |
| | IS TO REMAIN. PER WPB FBC 107.2.1, INDICATE HOW THE |
| | EXISTING TRAP SEAL PROTECTION IS TO REMAIN. IF |
| | CONDITIONS DO NOT ALLOW THE EXISTING PROTECTION TO |
| | REMAIN INTACT, PROVIDE NEW DETAIL/SPECIFICATION FOR |
| | TRAP SEAL PROTECTION COMPLYING WITH ONE OF THE |
| | FOLLOWING: FBC 1002.4.1.1, 1002.4.1.2, 1002.4.1.3 OR |
| | 1002.4.1.4. |
| | |
| | 8. PER WPB FBC 107.2.1 AND 107.3.5.1.3, CLEARLY SHOW ON |
| | THE WATER RISER DIAGRAM THE FOLLOWING: |
| | ?A) A WATER HAMMER ARRESTOR FOR THE HOT WATER TO THE |
| | DISHWASHER SHOWING COMPLIANCE WITH FBC PL 604.9. |
| | ?B) IDENTIFY THE DISHWASHER CONNECTION. |
| | ?C) PROVIDE SIZING FOR ALL NEW BRANCHES. |
| | |
| | 9. PER WPB FBC 107.2.1 AND 107.3.5.1.3, PROVIDE |
| | CALCULATIONS FOR SIZING OF WATER DISTRIBUTION AND |
| | SANITARY DRAINS. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |