| 2022-07-05 11:12:51 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21121211 2300 VILLAGE BLVD |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. SECOND REQUEST: PLAN SHEET A-1/CODE ANALYSIS: THE |
| | 2020 FLORIDA BUILDING CODES, SEVENTH EDITION INCLUSIVE |
| | OF FLORIDA BUILDING CODE ENERGY CONSERVATION, FLORIDA |
| | ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE |
| | 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS |
| | CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB |
| | FBC 107.2.1, PLEASE CORRECT. |
| | TO BE CLEAR, PROVIDE THE CURRENT EDITION DATE OF 2020 |
| | FOR THE APPLICABLE CODES |
| | NEW COMMENT: WPB AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE (2017), CHAPTER 1, ADMINISTRATION SHALL BE LISTED, |
| | NOT THE PALM BEACH COUNTY AMENDMENTS |
| | |
| | 2. COMPLIED |
| | |
| | 3. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE CONFIRM |
| | THAT THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER |
| | PIPING IS WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS |
| | DEFINED IN FBC PL 607.2. |
| | TO BE CLEAR, AN ACCEPTABLE SOURCE OF HOT WATER FOR HOT |
| | OR TEMPERED WATER IS A RECIRCULATING HOT WATER SYSTEM |
| | OR A HEAT TRACED PIPING SYSTEM, (OR A WATER HEATER) NOT |
| | A MIXING VALVE. FBC PL 607.2. |
| | PER WPB FBC 107.2.1, PLEASE CLARIFY ON THE PLANS. |
| | |
| | LINE ITEMS 4 THROUGH 14. COMPLIED |
| | |
| | NEW COMMENTS: |
| | |
| | 1. NEW COMMENT: SPECIFIED LEONARD 6020-LF SERVICING |
| | EYEWASH DOES NOT COMPLY WITH ASSE 1071 AS REQUIRED BY |
| | FBC PL 411.3. PER WPB FBC 107.2.1, PROVIDE COMPLIANT |
| | TMV. |
| | |
| | 2. NEW COMMENT: PER FBC PL 608.1, PROVIDE RPZ IN HOT |
| | WATER LINE TO TMV SERVICING THE P-1 DIALYSIS BOXES. |
| | |
| | 3. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| | SPECIFICATION AND DETAIL FOR RPZ, INCLUDING DISCHARGE |
| | WITH AIR GAP TO FLOOR SINK. |
| | |
| | 4. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE |
| | SPECIFICATION AND DETAIL FOR PRV WITH STRAINER TO |
| | REGULATE PRESSURE AT THE RPZ TO 25PSI MAX AS NOTED ON |
| | THE PLANS. COMPLY WITH FBC PL 604.8, 604.8.1 AND |
| | 604.8.2. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |