| Date |
Text |
| 2022-02-03 16:16:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21121211 2300 VILLAGE BLVD |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. PLAN SHEET A-1/CODE ANALYSIS: THE 2020 FLORIDA |
| | BUILDING CODES, SEVENTH EDITION INCLUSIVE OF FLORIDA |
| | BUILDING CODE ENERGY CONSERVATION, FLORIDA |
| | ACCESSIBILITY CODE 2020, FLORIDA EXISTING BUILDING CODE |
| | 2020, FLORIDA PLUMBING CODE 2020 AND FLORIDA FUEL GAS |
| | CODE 2020 7TH EDITION ARE THE APPLICABLE CODES. PER WPB |
| | FBC 107.2.1, PLEASE CORRECT. |
| | |
| | 2. PER WPB FBC 107.2.1, PROVIDE DEMO PLAN SHOWING THE |
| | CURRENT CONDITIONS AND DIRECTION FOR |
| | REMOVAL/REMEDIATION OF EXISTING PLUMBING FIXTURES, |
| | EQUIPMENT AND PIPING. |
| | |
| | 3. PER WPB FBC 107.2.1, PLEASE CONFIRM THAT THE |
| | DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING IS |
| | WITHIN 50 FEET OF THE SOURCE OF HOT WATER AS DEFINED IN |
| | FBC PL 607.2. |
| | |
| | 4. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING |
| | FIXTURE ITEM P-4/SHAMPOO SINK; SPECIFY AND PROVIDE |
| | MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION MANUAL |
| | FOR THE HAIR TRAP/INTERCEPTOR. INDICATE THE INTERCEPTOR |
| | ON THE PIPING PLANS AND PROVIDE A DETAIL. |
| | |
| | 5. PER WPB FBC 107.2.1, ADD FIXTURE TAG (I.E. P-1, P-2, |
| | ETC.) TO FIXTURES ON RISER DIAGRAMS AND RECONCILE WITH |
| | PLAN VIEW. |
| | |
| | 6. FIXTURE P-3 SINK COMES WITH EYEWASH INTEGRAL WITH |
| | THE FAUCET. WATER RISER DIAGRAM SHOWS EYEWASH AS A |
| | SEPARATE ENTITY WITH A TWO SEPARATE THERMAL MIXING |
| | VALVES, ONE FOR THE SINK FAUCET AND ONE FOR THE |
| | EYEWASH. PER WPB FBC 107.2.1, PLEASE CLARIFY. |
| | |
| | 7. PLAN SHEET P-1 AND P-2 SHOW THE P-5 EYEWASH AT |
| | OPPOSITE P-2 SINKS. PER WPB FBC 107.2.1, PLEASE CLARIFY |
| | AND RECONCILE. |
| | |
| | 8. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR PLUMBING |
| | FIXTURE ITEM P-1/DIALYSIS BOX. |
| | |
| | 9. PLAN SHEET P-1/PLUMBING GENERAL NOTE 8 REQUIRES PVC |
| | FOR SANITARY PIPING IF APPROVED BY LOCAL CODE, |
| | OTHERWISE USE CAST IRON. PRIOR TO INSPECTION, A PLAN |
| | REVISION REFLECTING THE ACTUAL MATERIAL SHALL BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT, APPROVED AND ON |
| | SITE. WPB FBC 107.2.1. |
| | |
| | 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | |
| | 11. PER WPB FBC 107.2.1, PROVIDE APPLICABLE RATED |
| | WALL/FLOOR DETAILS FOR PLUMBING PIPE PENETRATIONS |
| | COMPLYING WITH THE REQUIREMENTS OF FBC CHAPTER 7. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PIPE |
| | HANGER DETAIL STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 13. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR |
| | SIZING OF SANITARY AND WATER DISTRIBUTION. |
| | |
| | 14. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DIALYSIS |
| | EQUIPMENT. THIS MAY BE DONE AS A DEFERRED SUBMITTAL IN |
| | ACCORDANCE WITH WPB FBC 107.3.4.2. THE ITEMS SHALL BE |
| | LISTED ON THE PLANS AS DEFERRED SUBMITTALS TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL, APPROVED AND ON |
| | SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 21121211 2300 VILLAGE BLVD |
| | |