| Plan Review Notes For Permit 21121205 |
| Permit Number |
21121205 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-18 13:32:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE | | | LOCATION OF THE BATHROOMS WITHIN THE UNIT NOR IF THEY | | | ARE LOCATED ALONG A FIRE RATED TENANT | | | SEPARATION/CORRIDOR WALL REQUIRING MAINTENANCE/REPAIR | | | OF THE FIRE RATED WALL SHOULD THE DEMO DAMAGE THAT | | | WALL. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN | | | INDICATING THE LOCATION OF THE BATHROOM(S) AND A NOTE | | | OF ACKNOWLEDGEMENT TO MAINTAIN THE FIRE RATING OF THE | | | BATHROOM WALL IF APPLICABLE. | | | | | | | | | | | | 1A) THERE IS AN INDICATION OF TILE FLOOR, HOWEVER, TILE | | | FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT | | | CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE | | | VINYL/LAMINATE ETC AND IS MANUFACTURED FROM AROUND THE | | | WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND | | | NFPA STANDARDS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC | | | TILE TYPE AND/OR PRODUCT SPEC SHEETS IF VINYL/LAMINATE | | | . | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|