| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| | FL16709-R9 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| | ADDITIONAL INFORMATION: COVER SHEET |
| | (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE CODE |
| | VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL |
| | INFORMATION ABOUT THE PRODUCT). |
| | 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R9 SELECTED SYSTEM NO W-1; EXPOSURE |
| | (C); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ULTIMATE |
| | WIND SPEED IS 170 (MPH). THE CORRECT ENCLOSURE FOR THE |
| | LISTED ADDRESS IS ENCLOSED. ZONE 3 IS MARKED ?N/A? |
| | WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 |
| | PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. |
| | PLEASE SELECT THE CORRECT OPTIONS; CONSIDER USING |
| | FL16709-R9 SYSTEM NO. W-3; EXPOSURE C; CLOSED; ZONE 1 |
| | PRIME, ZONE 1 & ZONE 2 #1 (AS-LISTED), ZONE 3 #3; H < |
| | 15; 170 (MPH). |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |