| Plan Review Notes For Permit 21121125 |
| Permit Number |
21121125 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-02-04 15:41:58 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO, CFM | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT SIGNED AND SEALED WINDLOAD ENGINEERING FOR | | | THE PROPOSED LIGHT POLES WITH THE FIXTURES INCLUDED. | | | FBC CHAPTER 16 | | | | | | 2) PRVIDE DETAILS OF THE LIGHT POLES (IE. TYPE OF | | | MATERIAL, LENGTH, DIAMETER, HEIGHT ABOVE FINISH GRADE, | | | ETC.). FBC 107.2.1 | | | | | | 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | LIGHT POLES AND FIXTURES. FBC AMENDMENTS 107.2.1 | | | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | |
|