| Plan Review Notes For Permit 21121105 |
| Permit Number |
21121105 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-04-05 14:58:59 | 21121105 1501 PRESIDENTIAL WAY # 19 | | | | | | | | | PLUMBING COMMENTS: APPROVED | | | | | | | | | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | | INSPECTOR'S APPROVAL | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | PROVISO: SEE P-3/EWH & RECIRC PUMP DIAGRAM. DISCHARGE | | | FROM EXPANSION VALVE RELIEF OUTLET SHALL BE PIPED TO | | | THE PAN DRAIN OR MOP SINK THROUGH AN AIR GAP | | | | | | PROVISO: MANUFACTURER'S SPECIFICATION/INSTALLATION | | | MANUAL FOR THE BACKFLOW PREVENTER AT THE WATER | | | CONNECTION TO THE VACUUM PUMP SHALL BE ON SITE FOR | | | INSPECTION. | | | | | | |
|