Plan Review Notes
Plan Review Notes For Permit 21121105
Permit Number 21121105
Review Stop P
Sequence Number 2
Notes
Date Text
2022-03-10 14:59:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.SECOND REQUEST: ARCHITECT RESPONSE NOTED A.3/WALL
 FINISH SCHEDULE REVISED TO SPECIFY TILE FOR RESTROOM
 WALLS TO COMPLY WITH FBC 1210.2.2, FBC PL 310.3.
 SCHEDULE STILL INDICATES PAINT.
  
 2.NEW COMMENT: P.3/EWH & RECIRC PUMP DIAGRAM; REFER TO
 WATTS MANUFACTURER'S INSTALLATION GUIDE. COLD-WATER
 SUPPLY PIPE TO RISE TO A LEVEL EVEN WITH THE TOP OR
 ABOVE THE WATER HEATER WHERE THE DEVICE WILL BE
 INSTALLED IN A VERTICAL POSITION, THEN THEN PIPE DOWN
 AND INTO THE COLD-WATER INLET. INSTALLATION SHALL
 COMPLY WITH MANUFACTURER'S RECOMMENDATIONS PER FBC PL
 310.7 AND 303.2.
  
 3.SECOND REQUEST: P.3/EWH & RECIRC PUMP DIAGRAM;
 PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION
 THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3.
  
 4.P-4/WATER FILTER DETAIL
 ***A) SECOND REQUEST A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE WATER FILTER PER FBC PL
 604.9. PER WPB FBC 107.2.1, INDICATE ON DETAIL. TO BE
 CLEAR, THE WATER FILTER DETAIL SHOWS A SOLENOID VALVE.
 IF THIS IS A BALL VALVE THEN REMOVE REFERENCE TO A
 SOLENOID VALVE ON THE DETAIL
 ***B) NEW COMMENT/SECOND REQUEST: REGARDING THE CHECK
 VALVE/VACUUM BREAKER ON THE WATER INLET. ENGINEER'S
 RESPONSE IS THAT A WATTS 007 SERIES DOUBLE CHECK VALVE
 IS TO BE USED. PER WPB FBC 107.2.1, INDICATE THE SAME
 ON THE DETAIL.
  
 5.P-4/VACUUM PUMP DETAIL: ENGINEER'S RESPONSE NOTED
 BACKFLOW PREVENTION DEVICE IS FURNISHED BY THE
 EQUIPMENT SUPPLIER. A REVIEW OF THE SUBMITTAL SHEETS
 DOES NOT IN ANY WAY REFERENCE A BACKFLOW PREVENTER.
 REGARDLESS OF WHO PROVIDES THE DEVICE, IT STILL NEEDS
 TO BE SPECIFIED AND REVIEWED FOR APPROVAL.
 SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY TYPE OF
 BACKFLOW PREVENTER TO BE INSTALLED ON THE COLD-WATER
 CONNECTION. SHALL COMPLY WITH FBC PL 608.14.1,
 608.14.2, 608.14.5, 608.14.6 OR 608.14.8. PROVIDE
 APPLICABLE STANDARD (I.E. ASSE, ASME)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  