| 2022-03-10 14:59:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99-18 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21121105 1501 PRESIDENTIAL WAY # 19 |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1.SECOND REQUEST: ARCHITECT RESPONSE NOTED A.3/WALL |
| | FINISH SCHEDULE REVISED TO SPECIFY TILE FOR RESTROOM |
| | WALLS TO COMPLY WITH FBC 1210.2.2, FBC PL 310.3. |
| | SCHEDULE STILL INDICATES PAINT. |
| | |
| | 2.NEW COMMENT: P.3/EWH & RECIRC PUMP DIAGRAM; REFER TO |
| | WATTS MANUFACTURER'S INSTALLATION GUIDE. COLD-WATER |
| | SUPPLY PIPE TO RISE TO A LEVEL EVEN WITH THE TOP OR |
| | ABOVE THE WATER HEATER WHERE THE DEVICE WILL BE |
| | INSTALLED IN A VERTICAL POSITION, THEN THEN PIPE DOWN |
| | AND INTO THE COLD-WATER INLET. INSTALLATION SHALL |
| | COMPLY WITH MANUFACTURER'S RECOMMENDATIONS PER FBC PL |
| | 310.7 AND 303.2. |
| | |
| | 3.SECOND REQUEST: P.3/EWH & RECIRC PUMP DIAGRAM; |
| | PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION |
| | THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3. |
| | |
| | 4.P-4/WATER FILTER DETAIL |
| | ***A) SECOND REQUEST A WATER HAMMER ARRESTOR IS |
| | REQUIRED ON THE SUPPLY TO THE WATER FILTER PER FBC PL |
| | 604.9. PER WPB FBC 107.2.1, INDICATE ON DETAIL. TO BE |
| | CLEAR, THE WATER FILTER DETAIL SHOWS A SOLENOID VALVE. |
| | IF THIS IS A BALL VALVE THEN REMOVE REFERENCE TO A |
| | SOLENOID VALVE ON THE DETAIL |
| | ***B) NEW COMMENT/SECOND REQUEST: REGARDING THE CHECK |
| | VALVE/VACUUM BREAKER ON THE WATER INLET. ENGINEER'S |
| | RESPONSE IS THAT A WATTS 007 SERIES DOUBLE CHECK VALVE |
| | IS TO BE USED. PER WPB FBC 107.2.1, INDICATE THE SAME |
| | ON THE DETAIL. |
| | |
| | 5.P-4/VACUUM PUMP DETAIL: ENGINEER'S RESPONSE NOTED |
| | BACKFLOW PREVENTION DEVICE IS FURNISHED BY THE |
| | EQUIPMENT SUPPLIER. A REVIEW OF THE SUBMITTAL SHEETS |
| | DOES NOT IN ANY WAY REFERENCE A BACKFLOW PREVENTER. |
| | REGARDLESS OF WHO PROVIDES THE DEVICE, IT STILL NEEDS |
| | TO BE SPECIFIED AND REVIEWED FOR APPROVAL. |
| | SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY TYPE OF |
| | BACKFLOW PREVENTER TO BE INSTALLED ON THE COLD-WATER |
| | CONNECTION. SHALL COMPLY WITH FBC PL 608.14.1, |
| | 608.14.2, 608.14.5, 608.14.6 OR 608.14.8. PROVIDE |
| | APPLICABLE STANDARD (I.E. ASSE, ASME) |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |