Notes
Date Text
2022-03-15 11:03:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21121105
 ADD: 1501 PRESIDENTIAL WAY # 19
 CONT: PETRA BUILDERS GROUP
 TEL: 561-654-9987
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 15TH/2022
 ACTION: DENIED
  
 1)2ND REQUEST. RESPONSE INDICATES SEE SHEET A.3 FOR
 RESTROOMS AND A.1 FOR THE MOP SINK WITH FRP AROUND MOP
 SINK. BOTH SHEETS A.1 AND A.3 SHOW THE UPLOAD DATE OF
 1/5/2022 NO UPDATE NOR REVISION MARKER ON EITHER SHEET.
 SHEET A.3 SHOWS BOTH RESTROOMS 104 & 108 WITH ALL WALLS
 TO BE PAINTED AND WOOD BASE.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 1A) 2ND REQUEST. 1210.2.2 WALLS & PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 1B) 2ND REQUEST. 2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
 1C) 2ND REQUEST. 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2) 2ND REQUEST. SHEET A.3 SHOW THE UPLOAD DATE OF
 1/5/2022 NO UPDATE NOR REVISION MARKER ON SHEET A.3.
 SHEET A-3 SCHEDULES THE TELEPHONE OUTLET AND INTERCOM/
 PHONE ARE BOTH AT A HEIGHT OF 4 FEET 6 INCHES C/L ABOVE
 THE FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE
 REACH RANGES UNOBSTRUCTED FOR EITHER A FRONT APPROACH
 OR SIDE APPROACH. 2020 FBC-ACCESSIBILITY CODE:
 2A) 2ND REQUEST. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 2B) 2ND REQUEST. 309 OPERABLE PARTS. 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308. 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 3) SHEET A.5 CABINETRY ELEVATIONS:
 3A) 2ND REQUEST. DETAILS 3 WORK AREA, 4 WORK AREA WITH
 SINK , WORK AREA 6, LAB WORK AREA 10, WORK AREA WITH
 SINK 11 ALL SHOW THE CABINETRY COUNTER TOPS AT 36
 INCHES IN HEIGHT. ACCESS. CODE SECTION 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 SINKS SHALL ALSO BE NO MORE THAN 34 INCHES ABOVE FINISH
 FLOOR. 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3B)2ND REQUEST. DETAIL 11 ALSO SHOWS A MICROWAVE THE
 BOTTOM OF THE SHELF AT 4 FEET 10 INCHES ABOVE THE
 FLOOR. PLEASE SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 3B)(1). 2ND REQUEST. 308 REACH RANGES. 308.2 FORWARD
 REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH
 REACH. 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/
 308.3.2 OBSTRUCTED HIGH REACH.
  
 3B)(2) 2ND REQUEST. 309 OPERABLE PARTS. 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308. 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  