| 2022-01-18 15:33:10 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | NFPA 99-18 = HEALTH CARE FACILITIES CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21121105 1501 PRESIDENTIAL WAY # 19 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE ON THE PLANS, THE FOLLOWING |
| | CLARIFICATIONS: |
| | ?.A)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | "REFLECTING SURFACE" 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. |
| | ?.B)PROVIDE NOTE: PER FBC ACC602.7, SPOUT OUTLETS OF |
| | DRINKING FOUNTAINS FOR STANDING PERSONS SHALL BE 38 |
| | INCHES (965 MM) MINIMUM AND 43 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | |
| | 2.SEE FBC 1210.2.2, FBC PL 310.3. WALLS AND PARTITIONS |
| | WITHIN 2 FEET OF SERVICE SINKS AND WATER CLOSETS SHALL |
| | HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER |
| | FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES |
| | THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION |
| | IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A |
| | TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL |
| | COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE |
| | AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| | HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| | SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| | APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| | PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| | PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| | THE FINISH SCHEDULE CALLS OUT TWO PART EPOXY PAINT. |
| | THIS DOES NOT COMPLY. |
| | |
| | 3.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 4.PER WPB FBC 107.2.1, PROVIDE AT THE PIPE HANGER |
| | DETAIL A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| | SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| | |
| | 5.RE: WATER HEATER DETAIL.: PER WPB FBC 107.2.1, |
| | PROVIDE A MANUFACTURER SPECIFICATION/INSTALLATION |
| | MANUAL. INDICATE ON DETAIL BOTTOM FED OR TOP FED COLD |
| | WATER SUPPLY, NOTING VACUUM RELIEF VALVE OR COLD DIP |
| | TUBE AS IS APPLICABLE (SEE FBC PL 504.1, 504.2); |
| | PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION |
| | THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3. |
| | PROVIDE AIR GAP FOR T&P DISCHARGE TO PAN; SHALL |
| | TERMINATE NOT MORE THAN 6 INCHES) ABOVE AND NOT LESS |
| | THAN TWO TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE |
| | FLOOR OR FLOOD LEVEL RIM OF THE PAN PER FBC PL |
| | 504.6(10). |
| | |
| | 6.SLAB REPAIR DETAIL SUBMIT A SLAB REPAIR DETAIL SHOW |
| | THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE |
| | CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE. |
| | SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM |
| | EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING |
| | MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS |
| | ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE |
| | TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER |
| | OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE |
| | CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION. |
| | |
| | 7.WATER RISER: PER WPB FBC 107.2.1, SIZE ALL PIPING. |
| | |
| | 8.P-2/NOTE 21: PER WPB FBC 107.2.1, SELECT TRAP SEAL |
| | METHOD AND PROVIDE A DETAIL FOR THE TRAP PRIMER. |
| | |
| | 9.P-4/WATER FILTER DETAIL |
| | ?.A) A WATER HAMMER ARRESTOR IS REQUIRED ON THE SUPPLY |
| | TO THE WATER FILTER PER FBC PL 604.9. PER WPB FBC |
| | 107.2.1, INDICATE ON DETAIL. |
| | ?.B)DETAIL SHOWS A CHECK VALVE AND INDICATES A VACUUM |
| | BREAKER ON WATER INLET. PER WPB FBC 107.2.1, SPECIFY |
| | TYPE OF BACKFLOW PREVENTER (SEE FBC PL 608.1, TABLE |
| | 608.1) TO BE INSTALLED AT THE WATER FILTER INLET. |
| | PROVIDE ASSE OR CSA STANDARD. REVISE DETAIL TO REFLECT. |
| | |
| | 10.P-4/VACUUM PUMP DETAIL: |
| | PER WPB FBC 107.2.1, SPECIFY TYPE OF BACKFLOW PREVENTER |
| | TO BE INSTALLED ON THE COLD WATER CONNECTION. SHALL |
| | COMPLY WITH FBC PL 608.14.1, 608.14.2, 608.14.5, |
| | 608.14.6 OR 608.14.8. PROVIDE APPLICABLE STANDARD (I.E. |
| | ASSE, ASME) |
| | |
| | 11.PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION |
| | MANUAL FOR DENTAL EQUIPMENT |
| | |
| | 12.M-2/ NOTE 29 STATES SEE PLUMBING DRAWINGS FOR AC |
| | CONDENSATE. P-2/NOTE 13 PROVIDES AC CONDENSATE MATERIAL |
| | SPECIFICATION BUT NO PIPING IS SHOWN ON PLANS. THERE IS |
| | A NOTE 9 ON M-1 CALLING OUT 2 INCH DEEP TRAP WITH 3/4 |
| | INCH PVC TO EXISTING CONDENSATE RISERS. PER WPB FBC |
| | 107.2.1, PROVIDE ROUTING OF CONDENSATE DRAINS. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |