2022-01-18 15:33:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE ON THE PLANS, THE FOLLOWING
 CLARIFICATIONS:
 ?.A)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 "REFLECTING SURFACE" 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 ?.B)PROVIDE NOTE: PER FBC ACC602.7, SPOUT OUTLETS OF
 DRINKING FOUNTAINS FOR STANDING PERSONS SHALL BE 38
 INCHES (965 MM) MINIMUM AND 43 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2.SEE FBC 1210.2.2, FBC PL 310.3. WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER
 FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 THE FINISH SCHEDULE CALLS OUT TWO PART EPOXY PAINT.
 THIS DOES NOT COMPLY.
  
 3.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 4.PER WPB FBC 107.2.1, PROVIDE AT THE PIPE HANGER
 DETAIL A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 5.RE: WATER HEATER DETAIL.: PER WPB FBC 107.2.1,
 PROVIDE A MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL. INDICATE ON DETAIL BOTTOM FED OR TOP FED COLD
 WATER SUPPLY, NOTING VACUUM RELIEF VALVE OR COLD DIP
 TUBE AS IS APPLICABLE (SEE FBC PL 504.1, 504.2);
 PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION
 THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3.
 PROVIDE AIR GAP FOR T&P DISCHARGE TO PAN; SHALL
 TERMINATE NOT MORE THAN 6 INCHES) ABOVE AND NOT LESS
 THAN TWO TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE
 FLOOR OR FLOOD LEVEL RIM OF THE PAN PER FBC PL
 504.6(10).
  
 6.SLAB REPAIR DETAIL SUBMIT A SLAB REPAIR DETAIL SHOW
 THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING
 MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS
 ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 7.WATER RISER: PER WPB FBC 107.2.1, SIZE ALL PIPING.
  
 8.P-2/NOTE 21: PER WPB FBC 107.2.1, SELECT TRAP SEAL
 METHOD AND PROVIDE A DETAIL FOR THE TRAP PRIMER.
  
 9.P-4/WATER FILTER DETAIL
 ?.A) A WATER HAMMER ARRESTOR IS REQUIRED ON THE SUPPLY
 TO THE WATER FILTER PER FBC PL 604.9. PER WPB FBC
 107.2.1, INDICATE ON DETAIL.
 ?.B)DETAIL SHOWS A CHECK VALVE AND INDICATES A VACUUM
 BREAKER ON WATER INLET. PER WPB FBC 107.2.1, SPECIFY
 TYPE OF BACKFLOW PREVENTER (SEE FBC PL 608.1, TABLE
 608.1) TO BE INSTALLED AT THE WATER FILTER INLET.
 PROVIDE ASSE OR CSA STANDARD. REVISE DETAIL TO REFLECT.
  
 10.P-4/VACUUM PUMP DETAIL:
 PER WPB FBC 107.2.1, SPECIFY TYPE OF BACKFLOW PREVENTER
 TO BE INSTALLED ON THE COLD WATER CONNECTION. SHALL
 COMPLY WITH FBC PL 608.14.1, 608.14.2, 608.14.5,
 608.14.6 OR 608.14.8. PROVIDE APPLICABLE STANDARD (I.E.
 ASSE, ASME)
  
 11.PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR DENTAL EQUIPMENT
  
 12.M-2/ NOTE 29 STATES SEE PLUMBING DRAWINGS FOR AC
 CONDENSATE. P-2/NOTE 13 PROVIDES AC CONDENSATE MATERIAL
 SPECIFICATION BUT NO PIPING IS SHOWN ON PLANS. THERE IS
 A NOTE 9 ON M-1 CALLING OUT 2 INCH DEEP TRAP WITH 3/4
 INCH PVC TO EXISTING CONDENSATE RISERS. PER WPB FBC
 107.2.1, PROVIDE ROUTING OF CONDENSATE DRAINS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK TUESDAYS AND
 THURSDAYS