Plan Review Notes
Plan Review Notes For Permit 21121105
Permit Number 21121105
Review Stop MEDGAS
Sequence Number 1
Notes
Date Text
2022-01-18 15:35:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 1ST REVIEW
 MED GAS COMMENTS: DENIED
  
 1. P-4/COMPRESSOR DETAIL NOTE REFERENCING COPPER
 CATEGORY 3. PER WPB FBC 107.2.1, CLARIFY THE RISK
 CATEGORY AS DETERMINED BY NFPA 99-18; 15.1.1 THROUGH
 15.1.3 AND CONFIRM ON THE PLANS THE APPLICABLE "RISK
 CATEGORY". THE COMMENTS BELOW APPLY TO RISK CATEGORY 3.
 IF THE RISK CATEGORY IS OTHER THAN 3, ADDITIONAL
 COMMENTS WILL BE FORTHCOMING.
  
 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DENTAL
 EQUIPMENT AND COMPONENTS.
  
 3. PER WPB FBC 107.2.1, PROVIDE NOTE STATING
 MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION FOR
 BACKFLOW PREVENTER(S) SHALL BE ON SITE PRIOR TO
 INSPECTION.
  
 4. PER WPB FBC 107.2.1, PROVIDE A TRENCH BACKFILL
 DETAIL FOR UNDERGOUND PIPING SHOWING CLEAN SAND OR
 GRAVEL AS REQUIRED BY NFPA 99-18, SECTION 15.5.6.6.2.
  
 5. P-4/VACUUM NOTE 4 STATES NO DRAINAGE FITTINGS;
 DETAIL 4 AND 5 INDICATE DRAINAGE FITTINGS. PER WPB FBC
 107.2.1, CLARIFY.
  
 6. PER WPB FBC 107.2.1, PROVIDE COMPLETE MATERIAL
 SPECIFICATIONS FOR DENTAL AIR PIPING TO INCLUDE PIPE,
 FITTINGS AND JOINTS. SHOW COMPLIANCE WITH NFPA 99-18,
 SECTION 15.5.5.2.2 THROUGH 15.5.5.3.2.3.
  
 7. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DENTAL
 EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED TO
 OUTLETS, VALVES, GAUGES, CONTROLS.
  
 8. PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING
 SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE
 COMPONENTS
  
 9. PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL
 REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2
 THROUGH 5.1.3.7.6.5.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved