Plan Review Notes
Plan Review Notes For Permit 21121105
Permit Number 21121105
Review Stop M
Sequence Number 1
Notes
Date Text
2022-01-11 15:57:101ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21121105
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EF-1 BATH EXHAUST FANS MUST MEET MINIMUM VENTILATION
 CFM?S ACCORDING TO FBC M TABLE 403.3.1.1 FOOTNOTE F OF
 50 CFM CONTINUOUS OR 70 CFM?S INTERMITTENT
  
 2) PLEASE PROVIDE MORE INFORMATION AS TO WHAT IS BEING
 STORED IN THE MECHANICAL ROOM 115 AND STORAGE ROOM 116.
 EXPLAIN WHY THE EF-2 IS THERMOSTATICALLY CONTROLLED.
 FBC 107.2.1
  
 3) EXPLAIN WHY EF-1 IS TIED INTO THE SAME EXHAUST DUCT
 AS EF-2 FROM THE MECHANICAL ROOM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  