Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-01-07 10:41:17THE FLOOR PLAN DOOR 3 IS INDICATED AS AN EXIT. THE
 TREATMENT BAY CHAIR IN FRONT OF THIS DOOR APPEARS TO BE
 AN OBSTRUCTION TO EGRESS. NFPA 101 4.5.3.2
 FIRS SPRINKLER AND/OR FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMOLITION AND CONSTRUCTION. ANY
 WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  