| Notes |
| Date |
Text |
| 2022-01-07 10:41:17 | THE FLOOR PLAN DOOR 3 IS INDICATED AS AN EXIT. THE | | | TREATMENT BAY CHAIR IN FRONT OF THIS DOOR APPEARS TO BE | | | AN OBSTRUCTION TO EGRESS. NFPA 101 4.5.3.2 | | | FIRS SPRINKLER AND/OR FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMOLITION AND CONSTRUCTION. ANY | | | WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS | | | SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS. | | | |
|