2022-01-27 15:17:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) 1. VALUE FOR WORK STATED ON PERMIT APPLICATION
 APPEARS LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND
 LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED
 CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C.
 109.3
  
 2) PLEASE INDICATE WHICH PANEL OR PANELS THE GENERATOR
 WILL FEED.
  
 3) PLEASE INDICATE THE SIZE AND NUMBER OF CONDUCTORS
 GOING THROUGH THE NIPPLE BETWEEN METER AND TRANSFER
 SWITCH.
  
 4) PLAN DOES NOT REALLY INDICATE THE SIZE OF THE
 GENERATOR, PLEASE INDICATE THE SIZE OF THE GENERATOR.
  