| Plan Review Notes For Permit 21121087 |
| Permit Number |
21121087 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-01-27 15:17:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) 1. VALUE FOR WORK STATED ON PERMIT APPLICATION | | | APPEARS LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND | | | LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED | | | CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C. | | | 109.3 | | | | | | 2) PLEASE INDICATE WHICH PANEL OR PANELS THE GENERATOR | | | WILL FEED. | | | | | | 3) PLEASE INDICATE THE SIZE AND NUMBER OF CONDUCTORS | | | GOING THROUGH THE NIPPLE BETWEEN METER AND TRANSFER | | | SWITCH. | | | | | | 4) PLAN DOES NOT REALLY INDICATE THE SIZE OF THE | | | GENERATOR, PLEASE INDICATE THE SIZE OF THE GENERATOR. | | | |
|