Plan Review Notes
Plan Review Notes For Permit 21121087
Permit Number 21121087
Review Stop B
Sequence Number 1
Notes
Date Text
2022-03-09 16:19:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE
 CONCRETE PAD FOR WIND LOADS. FBC-R 301
  
 2) FBC-R303.5 OPENING LOCATION. OUTDOOR INTAKE AND
 EXHAUST OPENINGS SHALL BE LOCATED IN ACCORDANCE WITH
 SECTIONS R303.5.1 AND R303.5.2.
 THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. PLEASE SPECIFY
 THIS ON THE SURVEY.
  
  