| Plan Review Notes For Permit 21121087 |
| Permit Number |
21121087 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-03-09 16:19:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE | | | CONCRETE PAD FOR WIND LOADS. FBC-R 301 | | | | | | 2) FBC-R303.5 OPENING LOCATION. OUTDOOR INTAKE AND | | | EXHAUST OPENINGS SHALL BE LOCATED IN ACCORDANCE WITH | | | SECTIONS R303.5.1 AND R303.5.2. | | | THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10 | | | FEET FROM ANY OPENINGS INTO A BUILDING. PLEASE SPECIFY | | | THIS ON THE SURVEY. | | | | | | |
|