| Plan Review Notes For Permit 21121055 |
| Permit Number |
21121055 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-12-27 10:54:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON SHEET FA - 1 WITHIN THE | | | RISER DIAGRAM OF 5 DEVICES; 1-1 THRU 1-5. | | | | | | ON SHEET FA - 2 WITHIN THE FIRE ALARM PLAN THERE ARE 4 | | | DEVICES; 1-1 THRU 1-4. | | | | | | PLEASE REVIEW AND CORRECT ALL RELATED | | | AREAS/CALCULATIONS TO REFLECT THE ACTUAL PROPOSED | | | INSTALLATION. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|