Plan Review Notes
Plan Review Notes For Permit 21121055
Permit Number 21121055
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-12-27 10:54:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON SHEET FA - 1 WITHIN THE
 RISER DIAGRAM OF 5 DEVICES; 1-1 THRU 1-5.
  
 ON SHEET FA - 2 WITHIN THE FIRE ALARM PLAN THERE ARE 4
 DEVICES; 1-1 THRU 1-4.
  
 PLEASE REVIEW AND CORRECT ALL RELATED
 AREAS/CALCULATIONS TO REFLECT THE ACTUAL PROPOSED
 INSTALLATION.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  