| 2022-03-15 13:14:00 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21121052 |
| | 3/15/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THE COMMENTS BELOW ARE |
| | BASED ON THE RE-SUBMITTED PLANS AND RESPONSE NARRATIVE |
| | |
| | 1) SHEETS P1.1 & P1.2: AS DISCUSSED IN PHONE CALL WITH |
| | RGD ENGINEERS, THE DRAINAGE FROM THE GLASS WASHERS IN |
| | THE BAR AREAS SHALL DISCHARGE INTO THE GREASE WASTE |
| | LINE. FOR CLARIFICATION: FOOD AND BEVERAGE SERVICE |
| | SINKS INCLUDING 1, 2, OR 3-COMPARTMENT SINKS, |
| | DISHWASHERS AND GLASS WASHERS SHALL DRAIN INTO THE |
| | GREASE WASTE LINE- SEE SEC. 1003.3.1 FBC P. DRAINAGE |
| | FROM ICE MAKERS, ICE BINS, AND HAND SINKS SHALL DRAIN |
| | INTO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P. |
| | |
| | 2) P1.1 & P1.2: THE REVISED PLAN SHOWS A GREASE WASTE |
| | DRAIN LINE FROM FLOOR SINKS BELOW ICE CHEST 134 AND |
| | DRIP PAN 205 CONNECTING TO THE SANITARY. DOES THE |
| | DRAINAGE FROM THE DRIP PAN CONTAIN FATS, OIL, OR GREASE |
| | OR IS THE LINE MISLABLED- SEC. 1003.3.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |